          Programmable ControllerKV-8000 series

          Temperature Analog Multi-input Unit (Multi-input 4-channel)

          KV-TP40

          SPECIFICATIONS

          Select Language

          Model

          KV-TP40

          Type

          Temperature and analogue multi-input unit

          Number of temperature input points

          4 ch

          Input

          Thermocouple/Platinum temperature measuring resistor/Voltage and current

          Input range

          Thermocouple

          K: -270.0 to 1,372.0 °C
          J: -210.0 to 1,200.0 °C
          T: -270.0 to 400.0 °C
          E: -270.0 to 1,000.0 °C
          N: -270.0 to 1,300.0 °C
          R: -50.0 to 1,768.0 °C
          S: -50.0 to 1,768.0 °C
          B: 0.0 to 1,820.0 °C
          WRe5-26: 0.0 to 2,315.0 °C

          Platinum temperature measuring resistor

          Pt100: -200.0 to 850.0 °C
          JPt100: -200.0 to 600.0 °C

          Voltage and current

          Voltage:
          -10 to +10 V (0.5 mV 1/40,000)
          0 to 10 V (0.5 mV 1/20,000)
          -5 to +5 V (0.5 mV 1/20,000)
          0 to 5 V (0.5 mV 1/10,000)
          1 to 5 V (0.5 mV 1/8,000)
          -100 to +100 mV (5 µV 1/40,000)
          0 to 100 mV (5 µV 1/20,000)
          Current:
          0 to 20 mA (2 µA 1/10,000)
          4 to 20 mA (2 µA 1/8,000)

          Indicated accuracy

          ±0.2 % of F.S. (25 ±5 °C), ±0.4 % of F.S. (0 to 50 °C)

          Cold junction correction precision

          ±1 °C (during thermocouple input)

          Conversion speed

          50 ms/4 ch

          Insulation mode

          Between an input terminal and CPU: Photocoupler transformer insulation,
          Between channels: Photocoupler transformer insulation

          Other functions

          External cold junction correction, wire-breaking detection function, scaling function,
          average processing function (time average, average of the number of times, moving average, primary delay filter)
          Special data offset function, alarm function, rate of change calculation, rate of change alarm function

          Internal current consumption

          90 mA or less

          Weight

          Approx. 190 g

          • PLC/HMI User Support
          • General Catalogue Request
          • Trade Shows and Exhibitions
          • eNews Subscribe

          Back to top

          KEYENCE SINGAPORE PTE LTD. 151 Lorong Chuan,#05-07, New Tech Park Lobby G, Singapore 556741
          Phone: +65-6392-1011
          E-mail: info@keyence.com.sg
          Career Opportunities: KEYENCE Career Site

          Controls