Touch Panel Display
VT3 series
7-inch VGA TFT Colour Free-layout Panel VT3-V7R
 
*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.
Specifications
| Model | VT3-V7R | |||
| General specifications | Current consumption | 550mA or less | ||
| Structure | IP65f equivalent dust proof, waterjet proof | |||
| Overvoltage category | I | |||
| Pollution degree | 3 | |||
| Power voltage | 24 VDC ±10% | |||
| Noise resistance | 1500 Vp-p pulse width 1 µs 50 ns (common mode, based on noise simulator) | |||
| Withstand voltage | 1500 VAC 1 minute (between power terminal and housing) | |||
| Insulation resistance | 50 MΩ or more tested by 500 VDC megohmmeter (between power terminal and housing) | |||
| Vibration resistance | Intermittent vibration | Frequency: 5 to 9 Hz | Half amplitude:3.5 mm*1 | |
| Frequency: 9 to 150 Hz | Acceleration: 9.8 m/s2 *1 | |||
| Continuous vibration | Frequency: 5 to 9 Hz | Half amplitude:1.75 mm*1 | ||
| Frequency: 9 to 150 Hz | Acceleration: 4.9 m/s2 *1 | |||
| Ground | Class D grounding (Class 3 grouding). | |||
| Operating environment | Minimal amount of dust and corrosive gas present | |||
| Ambient operating temperature | 0 to +50°C | |||
| Ambient operating humidity | 35 to 85%RH (No condensation)*2 | |||
| Ambient storage temperature | -10 to +60°C (No freezing) | |||
| Ambient storage humidity | 35 to 85%RH (No condensation)*2 | |||
| Weight | Approx 1,600 g (excluding the cable) | |||
| Performance specifications | Displaypanel | Display elements | TFT colour LCD | |
| Display colour | 32768 colours | |||
| Number of points displayed | W 640 × H 480 points | |||
| Active display area | W 151.7 × H 113.8 mm | |||
| Service life (normal temperature andhumidity) | Approx 50000 h | |||
| Backlightlamp | System | Cold-cathode tube (Not replaceable) | ||
| Life-span | Approx 54000 h | |||
| Touchswitch | Number of switches | 40×30/screen | ||
| System | Matrix resistive film | |||
| Operating force | 0.98N or less | |||
| Life-span | 1,000,000 times or more | |||
| External calibration input signal | Pressure-sensitive type | |||
| Screen data internal memory | Memory capacity | 12 MB (memory extension enabled) | ||
| Number of pages that can be registered | Up to 1024 pages | |||
| Number of screens that can be registered | Up to 1024 screens | |||
| Page No.: 0 to 8999, Global window No.: G000 to G999, Report screen P.00 to P.15 | ||||
| Data backup | Screen data | Flash ROM can be erased 100000 times. | ||
| Recording data | SRAM backup:lithium battery | |||
| Character font | Outline font, Bitmap font, Stroke font Windows font, IMAGE font, Small font | |||
| Calendar timer | Accuracy: ±40s/month (25°C), Backup:lithium battery (5 years above of service life at 25°C) | |||
| Communication function | PLC host link | KEYENCE, Mitsubishi Electric, OMRON, Sharp, Fuji Electric FA Components & Systems, Yaskawa Electric, Hitachi, Panasonic Electric Works, JTEKT (Toyota), | ||
| Thermostat | Yokogawa Electric, Azbil (Yamatake), OMRON, RKC Instrument, Shinko Technos, CHINO | |||
| Inverter | Mitsubishi Electric, Fuji Electric FA Components & Systems, Yaskawa Electric, OMRON | |||
| Servo amplifier | Mitsubishi Electric | |||
| Stepping motor | Orienltal Motor | |||
| Robot controller | IAI | |||
| Eco-power meter | Panasonic Electric Works | |||
| General-purpose communication | Based on specific commands | |||
| Grip switch | Life-span | 50,000 times or more | ||
| Arrow keys | 100,000 times or more | |||
| I/O specifications | Serial I/F (PORT 1: SERIAL) for connecting PCs | Applied standard | ― | |
| Synchronisation between the transmitter and receiver | ||||
| Communication distance | 15m | |||
| Data length | ― | |||
| Parity | ||||
| Communication speed | ||||
| Serial I/F (PORT 2) for connecting PLC/external devices | Applied standard | |||
| Synchronisation between the transmitter and receiver | ||||
| Communication distance | 15m (RS-232C)/500m (RS-422A) | |||
| Data length | ― | |||
| Parity | ||||
| Communication speed | ||||
| Serial I/F (PORT 3) for connecting barcode/PLC/external devices | Applied standard | |||
| Synchronisation between the transmitter and receiver | ||||
| Communication distance | ||||
| Data length | ||||
| Parity | ||||
| Communication speed | ||||
| Serial I/F (PORT 4) for connecting MegaLink/multi-link/KL-link/external devices | When connected through MegaLink | Applied standard | RS-485 | |
| Synchronisation between the transmitter and receiver | ― | |||
| Communication speed | ||||
| Cable connection | ||||
| Maximum number of connectable units | ||||
| Baud rate 19200 | ||||
| Baud rate 115200 | ||||
| Baud rate 0.5 M | ||||
| Baud rate 1 M | ||||
| Baud rate 2 M | ||||
| When connected through VT2 multi-link | Applied standard | RS-485 | ||
| Synchronisation between the transmitter and receiver | ― | |||
| Communication distance | ||||
| Communication speed | ||||
| Baud rate 115200 or less | ||||
| Baud rate 0.5 M | ||||
| Baud rate 1 M | ||||
| When connected through multi-link | Applied standard | RS-485 | ||
| Synchronisation between the transmitter and receiver | ― | |||
| Communication distance | ||||
| Communication speed | 19200, 38400, 57600, 115200 bit/s | |||
| When linked with the KL | Sign system | ― | ||
| Control method | ||||
| Cable connection | ||||
| Communication speed | ||||
| Communication media | ||||
| Maximum number of connectable units | ||||
| Error control | ||||
| Baud rate 5 Mbit/s: Maximum base length | 50 m | |||
| Baud rate 5 Mbit/s: Maximum branch wire length | 20 m | |||
| Baud rate 2.5 Mbit/s: Maximum base length | 120 m | |||
| Baud rate 2.5 Mbit/s: Maximum branch wire length | 40 m | |||
| Baud rate 625 kbit/s: Maximum base length | 500 m | |||
| Baud rate 625 kbit/s: Maximum branch wire length | 150 m | |||
| Baud rate 156 kbit/s: Maximum base length | 1200 m | |||
| Baud rate 156 kbit/s: Maximum branch wire length | 350 m | |||
| Communication cable conductor section area 0.5 mm2 | ― | |||
| Communication cable conductor section area 0.75 mm2 | ||||
| Communication cable conductor section area 0.9 mm2 | ||||
| Communication cable conductor section area 1.25 mm2 | ||||
| *1 Conforms to JIS B 3502, IEC61131-2 | ||||
 