Panel-mounted PLC with Built-in Display Functions
KV-P series
Contact Us: 1800-396-5010(Singapore) +65-6392-1011 Enquiry form
Base unit, DC type, 10 Inputs and 6 Relay Outputs KV-P16R
*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.
Specifications
Model | KV-P16R | |||
General specifications | Environmental resistance | Operating ambient temperature | 0 to 50°C (no freezing)*1 | |
Operating ambient humidity | 35 to 85%RH (no condensation) | |||
Ambient temperature for storage | -20 to 70°C (no freezing) | |||
Withstand voltage | 1,500 VAC for 1 minute (between the power supply terminal and the I/O terminals and between all the external terminals and the case) | |||
Noise immunity | 1,500 Vp-p or more, pulse width: 1 µs, 50 ns (by way of a noise simulator) | |||
Ambient operating atmosphere | Minimal amount of dust and corrosive gas present | |||
Overvoltage category | I | |||
Allowable instantaneous outage time | Less than 2 ms | |||
Structure | Panel-mount type, only the operation part of the front surface has a rating of IP65. | |||
Power voltage | 24 VDC ± 10% | |||
Internal current consumption | 220mA or less | |||
Environmental resistance | Insulation resistor | 50 MΩ or more (tested with a 500 VDC megger, between the power supply terminal and the I/O terminals and between all the external terminals and the case) | ||
Impact resistance | Conforms to JIS B 3502 and IEC 61131-2, 147 m/s2, operating time: 11 ms, 3 times in each of the 3 directions | |||
Pollution degree | 2 | |||
Vibration resistance | Intermittent vibration | Frequency: 10 to 57 Hz | Amplitude: 0.075 mm*2 | |
Frequency: 57 to 150 Hz | Acceleration: 9.8 m/s2*2 | |||
Continuous vibration | Frequency: 10 to 57 Hz | Amplitude: 0.035 mm*2 | ||
Frequency: 57 to 150 Hz | Acceleration: 4.9 m/s2*2 | |||
Weight | Approx 415g | |||
Function specifications | Data access panel | Display power | LCD display with 3-colour backlight | |
Character size | Full-width: 7.00 mm × 7.80 mm, half-width: 3.48 mm × 7.80 mm | |||
Data name display | Negative and positive displays, blinking display, scroll display Half-width characters: fixed display: 14 characters, scroll display: 64 characters Full-width characters: fixed display: 7 characters, scroll display: 32 characters | |||
Data display | Sign, up to 10 digits with decimal point | |||
Display device | All devices (registered with the panel editor) | |||
Data change | By way of the front panel switch | |||
Reset function | By way of the RESET switch | |||
Key protection function | By way of the front panel switch | |||
Other | Indirect specification can be used to display messages. | |||
Message panel | Display power | LCD display with 3-colour backlight | ||
Character size | Full-width: 7.00 mm × 7.80 mm, half-width: 3.48 mm × 7.80 mm | |||
Message view | Negative and positive displays, blinking display, scroll display Same size half-width characters: fixed display: 14 characters, scroll display: 64 characters Same size full-width characters: fixed display: 7 characters, scroll display: 32 characters Same size vertical half-width characters: fixed display: 14 characters, scroll display: 64 characters, Same size vertical full-width characters: fixed display: 7 characters, scroll display: 32 characters ×4 half-width characters: fixed display: 7 characters, scroll display: 64 characters ×4 full-width characters: fixed display: 3 characters, scroll display: 32 characters (When same size vertical characters or ×4 characters are displayed, the second line cannot be used to display nameplates.) | |||
Nameplate display | 2 full-width characters (4 half-width characters) × 3 nameplates, positive display | |||
Function switch | F1 to F5, 5 total (F2 to F4 have nameplate displays.) | |||
Other | Indirect specification can be used to display data. | |||
Performance specifications | Arithmetic control method | Stored program method | ||
I/O control method | Refresh method | |||
Programming language | Ladder chart method + expansion ladder method | |||
Instruction type | Basic instructions: 28 kinds, application instructions: 22 kinds, calculation instructions: 26 kinds, interrupt instructions: 4 kinds | |||
Minimum scan time | 140 µs | |||
Instruction processing speed | Basic instruction | 0.7 µs minimum | ||
Application instruction | 6.4 µs minimum | |||
Program capacity | 4,000 steps | |||
Expansion unit: Maximum number of units that can be attached | 8 (excluding the QL-B1) | |||
KL interface | None | |||
Number of inputs/outputs (the KV-P main unit, includes 16 inputs/outputs) | 16 to 2,064 (when extended to the maximum number of KL Series units), 16 to 272 (when extended to the maximum number of QL Series units), 16 to 144 (when extended to the maximum number of expansion units) | |||
Internal auxiliary relay | 2,560 relays, 1,000 to 1,915 and 3,000 to 17,915 (including the relays for the QL Series) | |||
Special auxiliary relay | 160 relays, 2,000 to 2,915 | |||
Data memory | 2,000 words, DM0000 to DM1999 | |||
Temporary data memory | 32 words, TM00 to TM31 | |||
Timer/counter | 0.1 s timer: TMR (0 to 6,553.5 s) 0.01 s timer: TMH (0 to 655.35 s) 0.001 s timer: TMS (0 to 65.535 s) Addition counter C Up/down counter UDC Total: 250 | |||
Digital trimmer | 2 | |||
High-speed counter | 30 kHz, 2-phase high-speed counter × 2 (count from 0 to 65,535)*3 | |||
High-speed counter comparator | 4 (2 equipped for each high-speed counter), direct output possible | |||
Positioning control function | 1 independent axis, 50 kHz maximum | |||
Memory switch | 16 | |||
Power off holding function | Program memory | Flash ROM rewritable 100,000 times or more | ||
Data memory, counter, internal auxiliary relay, contact comment (retention devices are set by MEMSW instructions) | 120 days or more (at 25°C) through use of electric double-layer capacitors, flash ROM can be used to back up data | |||
Self-diagnosis function | CPU error, RAM error | |||
Peripheral equipment | Programming console KZ-P3, ladder support software KV BUILDER (version 4 or later) | |||
Number of contact comments | 1,000 contact comments maximum can be recorded | |||
*1 These are the values when installed with a vertical orientation. Refer to the instruction manual for details on all other installations. |