Programmable Logic ControllerKV-7000 series

KV-SDA04

High-speed analogue output unit

SPECIFICATIONS

Select Language

Model

KV-SDA04*1

General specifications

Type

Expansion Unit (High-speed analogue output unit)

Supply voltage

KV-5000/3000 Series System configuration using an expansion unit : 24 V DC (±10%)*2
KV-7000 Series System configuration with only an expansion unit : 24 V DC (-15% / +20%)*2

Environmental resistance

Withstand voltage

1500 VAC for 1 minute
(between the power terminals and the I/O terminals, and between the external terminals and the housing)

Noise immunity

1500 Vp-p or more
Pulse width: 1 µs, 50 ns
(based on noise simulator)
IEC standard-compliant
(IEC 61000-4-2/3/4/6)

Vibration resistance

Intermittent vibration: Frequency 5 to 9 Hz

Half amplitude 3.5mm*3

Intermittent vibration: Frequency 9 to 150 Hz

Acceleration: 9.8m/s2*3

Continuous vibration: Frequency 5 to 9 Hz

Half amplitude 1.75mm*3

Continuous vibration: Frequency 9 to 150 Hz

Acceleration: 4.9m/s2*3

Operating surrounding air temperature

KV-5000/3000 Series System configuration using an expansion unit : 0 to +50°C (No freezing)*4*5
KV-7000 Series System configuration with only an expansion unit : 0 to +55°C (No freezing)*4*5

Operating ambient humidity

KV-5000/3000 Series System configuration using an expansion unit : 10 to 95% RH (No condensation)*4
KV-7000 Series System configuration with only an expansion unit : 5 to 95% RH (No condensation)*4

Storage ambient temperature

KV-5000/3000 Series System configuration using an expansion unit : -20 to 70°C*4
KV-7000 Series System configuration with only an expansion unit : -25 to 75°C*4

Storage ambient humidity

KV-5000/3000 Series System configuration using an expansion unit : 10 to 95% RH (No condensation)*4
KV-7000 Series System configuration with only an expansion unit : 5 to 95% RH (No condensation)*4

Operating environment

No dust or corrosive gas

Environmentalresistance

Operating altitude

2000m or less

Environmental resistance

Insulation resistor

50 MΩ or more
(between the power terminals and the I/O terminals, and between the external terminals and the housing, with 500 VDC megohmmeter)

Impact resistance

Acceleration: 150m/s2, Operation time: 11 ms, 2 times in each of the X, Y, and Z directions

Pollution degree

2

Performance specifications

Conversion speed

10 µs/ch

Isolation mode

Between analogue output and CPU: Isolated (photocoupler, transformer)
Between analogue output channels: Non-isolated

Internal current consumption

170 mA or less

Weight

Approx. 140 g

Input resistance

Conversion precision

±0.1% (25°C ±5°C), ±0.2% (0 to 55°C)
(precision per range)

Absolute max. input

Minimum load resistance

Voltage: 1kΩ

Maximum load resistance

Current : 500Ω

Analogue input point

4 points

Analogue output point

Analogue input range (resolution)

Voltage:
-10 to +10V (0.5mV, 1/40000)
0 to 10V (0.5mV, 1/20000)
0 to 5V (0.25mV, 1/20000)
1 to 5V (0.25mV, 1/16000)
Current:
0 to 20mA (1µA, 1/20000)
4 to 20mA (1µA, 1/16000)

Analogue output range (resolution)

*1 For KV-7000 Series
*2 Supplied via CPU unit or other Expansion unit
*3 Compliant with JIS B 3502 and IEC 61131-2, Number of scanning operations: 10 times in each of the X, Y, and Z directions (for 100 min.)
*4 Guaranteed range in which the system can be used.
*5 Specified according to the temperature in the control panel on the lower side of the unit.