Programmable Logic ControllerKV-7000 series

KV-PU1

AC Power Supply Unit with Error Output

SPECIFICATIONS

Select Language

Model

KV-PU1*1

General specifications

System

Switching type

Input supply voltage

100 to 240 VAC (+10%/-15%) (50/60 Hz)

Output voltage

24 VDC ±10%

Output capacity

1.8 A (total power supply to various units and extra power supply)

Momentary stop time

20 ms or less (depending on rated I/O conditions)

Power-on reset time

Max. 3 sec. or less

Environmental resistance

Withstand voltage

3,000 V AC for 1 min. (between input and output)

Noise immunity

1500 Vp-p or more
Pulse width: 1 µs, 50 ns
(based on noise simulator)

Vibration resistance

Intermittent vibration: Frequency 5 to 9 Hz

Half amplitude 3.5mm*2

Intermittent vibration: Frequency 9 to 150 Hz

Acceleration: 9.8m/s2*2

Continuous vibration: Frequency 5 to 9 Hz

Half amplitude 1.75mm*2

Continuous vibration: Frequency 9 to 150 Hz

Acceleration: 4.9m/s2*2

Operating surrounding air temperature

0 to 55°C (no freezing)*3*4

Operating ambient humidity

5 to 95% RH (No condensation)*3

Storage ambient temperature

-40 ~ +75 °C*3

Storage ambient humidity

5 to 95% RH (No condensation)*3

Operating environment

No dust or corrosive gas

Environmentalresistance

Operating altitude

2000m or less

Environmental resistance

Insulation resistor

50 MΩ or more
(500 V DC mega between all external terminals and case)

Impact resistance

Acceleration: 150m/s2, Operation time: 11 ms, 2 times in each of the X, Y, and Z directions

Pollution degree

2

Environmentalresistance

Overvoltage category

II

Performance specifications

Response time

When turning OFF → ON: 10 ms or less
When turning ON → OFF: 5 ms or less

Output form

Relay (NC contact)

Rated load

24 VDC 0.5 A

ON resistance

50mΩ or less

Relay life

Electrical: 100000 times or more (20 times/min.), Mechanical: 20 million times or more

Relay replacement

Impossible

Internal current consumption

0.96A or less

Weight

Approx. 300 g

*1 For KV-7000 Series
*2 Compliant with JIS B 3502 and IEC 61131-2, Number of scanning operations: 10 times in each of the X, Y, and Z directions (for 100 min.)
*3 Guaranteed range in which the system can be used.
*4 Specified according to the temperature in the control panel on the lower side of the unit.

For visitors who viewed this page

    • PLC/HMI User Support

    Latest / Most Downloaded

      • General Catalogue Request
      • Trade Shows and Exhibitions
      • eNews Subscribe

      Controls