General Specifications

Power voltage

10.8 to 26.4 VDC (for the connector type I/O unit, this is supplied by the dedicated cable)

Operating ambient temperature

0 to 60°C

Operating ambient humidity

35 to 85%RH (no condensation)

Withstand voltage

500 VAC for 1 minute (between the power supply terminal and the I/O terminals; excluding the ERR output terminal)

Noise immunity

Power supply common: 1,500 V, power supply normal: 500 V, pulse width: 1 ms, 50 ns (by way of a noise simulator)

Insulation resistance


Operating environment

No corrosive gas present

General specifications

Disconnection error output load

30 VDC, 0.1 A or less, residual voltage: 1 V or less

Vibration resistance

10 to 55 Hz, 1.5 mm or less double amplitude for 2 hours in each of the X, Y, and Z directions; 1 G when attached to a DIN rail

Input specifications

Insulation system


Input maximum rating

Performance specifications

Input voltage

Minimum ON voltage

Maximum OFF current

Input specifications

Maximum OFF voltage

Performance specifications

Input impedance

Number of inputs/outputs

16-connector transistor output

Internal current consumption

70mA or less


approx 70g

Output specifications


NPN open collector

Residual voltage (when output is ON)

0.8V or less

Leakage current (when output is OFF)

100 µA or less

transistor output

Rated load voltage

30 V DC and
5 to 26.4 V DC (power source supplied across VC and C)

Rated output current

0.5 A/output (when 24 V or more is applied across VC and C), 0.15 A/output (when 12 V or more is applied across VC and C), 0.05 A/output (when 5 V or more is applied across VC and C)

Common ground

Written on the terminal wiring diagram of each unit

ON delay time

25 µs or less

OFF delay time

200 µs or less

Insulation resistance

20 MΩ or more (tested with a 500 VDC megger, between the power supply terminal and the I/O terminals; excluding the ERR output terminal)

Insulation system

Photocoupler isolation

relay output

Rated voltage


Rated output current

Common ground

ON resistance

ON delay time

OFF delay time

Insulation resistance

Insulation system

For visitors who viewed this page

    • PLC/HMI User Support

    Latest / Most Downloaded

      • General Catalogue Request
      • Trade Shows and Exhibitions
      • eNews Subscribe